Did you know that a 50-amp pedestal is actually 100 amps?

Everyone,

I found this post on the RV Hacking Camping group. And while it’s not dangerous (or shouldn’t be if wired correctly) it’s certainly not equal to a 50-amp outlet. And here’s why…

What is happening here?

You can buy a double TT-30 Male to RV-50 (NEMA 14-50) Y cable most anywhere. And if the pedestal is wired properly (without a reverse polarity on one of the outlets) it should be safe. But be aware that the campground didn’t plan for you to use it that way, and you’re using more electricity than was built into your campsite rate.

But is it 50-amps?

Not really, because a 50-amp pedestal outlet is actually 100 amps at 120 volts (50 amps for hot leg-1 plus 50 amps for hot leg 2 equals 100 amperes).

But the double 30 amp adapter is actually 60 amps at 120 volts (30 amps for hot leg-1 plus 30 amps for hot leg-2 equals 60 amperes). So it’s close, but not exactly the same thing. Still, it should work as long as the pedestal is wired properly and the campground allows it.

Here’s how a 50-amp outlet is actually wired

Much more on this later

Let’s Play safe out there… Mike

8 thoughts on “🟦 Why two 30’s don’t make a 50!”

    1. Campground pedestals that have two 30 amp receptacles separated by two 20 amp receptacles used to be quite common in area campgrounds near me where the pedestals were shared by two campsites – I can think of one really popular campground in our area that this was (or maybe still is if they haven’t upgraded) the normal for the majority of their campsites that didn’t have 50 amp receptacles, and some posts had double everything 2 50’s 2 30’s and sometimes even two 20’s so that they could still be shared. I remember the fun of when some would just flip off all the breakers in the box as they were leaving because that turned off power to your unit also (I’m not always certain that was unintentional).

  1. Interesting, thanks Mike! The pedestals I’ve seen either have a 20A, 30A, and 50A outlet (and a breaker for each) or they only have 20A and 30A outlets, but why does this one seem to have a 20A outlets and 2-30A outlets on either side of it? I may be missing something and, if so, why do they do this? Other questions come to mind as well but hopefully Mike will tell us more.

    1. Campground pedestals that have two 30 amp receptacles separated by two 20 amp receptacles used to be quite common in area campgrounds near me where the pedestals were shared by two campsites – I can think of one really popular campground in our area that this was (or maybe still is if they haven’t upgraded) the normal for the majority of their campsites that didn’t have 50 amp receptacles, and some posts had double everything 2 50’s 2 30’s and sometimes even two 20’s so that they could still be shared. I remember the fun of when some would just flip off all the breakers in the box as they were leaving because that turned off power to your unit also (I’m not always certain that was unintentional).

      1. Thanks Jim! Makes sense that this is for a shared pedestal. I only saw one 20A outlet in the picture but the other one might have been obscured by the camera angle or the large 30A plugs.

  2. hello,
    How do you feel about an RV that has a 50 amp receptacle on it, but it has 2 – 30 amp breakers in the box and the wire itself is smaller and stranded? Does the math work the same way in the rv’s case?
    Thanks