What is a Reverse Polarity Bootleg Ground?

This is the most dangerous of all miswiring conditions which can’t be detected by any surge protector!

Dear Mike,

I’ve read all the articles you’ve written about Reverse Polarity Bootleg Grounds but was unable to post a comment, since they are more than a year old! My question, which I don’t believe was answered in the articles, is this:

Are surge protector companies, like Progressive, working to fix this problem in their products so they do detect this condition? Appreciate your comments! Thanks! —Jeff

Dear Jeff,

I’m happy to provide a few updates. But in the meantime, let’s review what an RPBG (Reverse Polarity Bootleg Ground) is and why it’s dangerous.

This is a dangerous miswiring condition that I discovered and named more thn 10 years ago, and it’s important to understand since an RPBG can sometimes be found in 1970s or earlier era houses, garages, performance stages, churches and campgrounds. If you plug your RV into an outlet miswired with an RPBG, then you’re creating a life-threatening condition.

What’s an RPBG?

But first here’s a picture of how and why this condition exists in the first place. If you look at the leftmost outlet above (Labeled Correct Ground), you’ll see that it’s wired correctly with a green/ground wire, white/neutral wire, and a black/hot wire. All houses, stages and campground outlets since the early 1970s are supposed to be wired like that. And probably 99.99% of them are wired correctly.

But if you’ve ever done any wiring in an old house, stage, boat dock or even campground, you’ll find that the green ground wires didn’t exist in the 1960s or before. That’s because the National Electrical Code didn’t require any kind of ground conductor at that point in time. So that’s when ungrounded, 2-prong, polarized outlets were installed everywhere..

Modern wiring

However, by the early ’70s the National Electrical Code changed and all new installations were required to install 3-prong grounded receptacles with 15- or 20-amp capacity. But since there were no preexisting ground wires already run in the walls, some electricians and DIY guys would do something called a “Bootleg Ground,” which you can see in the middle outlet of the next diagram. That is, they would simply jumper the ground screw on the back of the outlet over to the neutral wire.

While that’s a huge code violation, in many cases there’s no immediate danger, and many older installations still have upgraded grounded outlets with bootleg grounds. I’ll just note that this is a dangerous practice and any discovered bootleg ground outlets should be corrected by running new wiring that includes a ground conductor (formally called an EGC for Equipment Grounding Conductor). Note that it’s also possible to install a Class-A GFCI receptacle that’s not-grounded, and it will pass code. But it’s supposed to be marked as ungrounded.

However, if you do make a bootleg ground and also happen to get the Hot/Neutral polarity reversed at the same time, then you create something I call a Reverse Polarity Bootleg Ground, or RPBG for short. That’s shown in the rightmost outlet of the above diagram.. It’s probably the most dangerous kind of miswiring condition you’ll ever encounter since it does two things.

Why is an RPBG so dangerous?

First, an RPBG outlet will energize the skin, chassis, tow vehicle and virtually everything plugged into or connected to your RV with a 120 volts of hot-skin/contact-voltage, and with at least 20 amps of current behind it. But the RV and all its appliances will operate normally with no warning signs of an energized surface. So no sparks, no blue glow, no hum, and no other special effects you might see in the movies.

And as you can see in the picture from my lab bench, a 3-light outlet tester will tell you the outlet is OK, when in fact the ground and chassis/skin of your RV is sitting at 120 volts of potential. There are simply no warning signs.

Standard meter tests won’t find an RPBG

Second, an RPBG is not discoverable by any standard meter test, 3-light outlet tester, or even the most expensive EMS surge protectors on the market. Note that if you measure H-G, G-N and H-N the voltages are exactly the same as a properly wired outlet. You have to measure against an external ground reference to find an RPBG with a voltmeter.

While Progressive initially told their customers that their products could detect and disconnect an RV from the hot ground voltage of an RPBG outlet, once I sent my schematics to their engineering department and had them build a test unit, they called me back to let me know I was correct. They never realized such a condition could exist in the wild, and their EMS surge protectors were helpless to warn you about the condition.

RPBG outlets in the wild

I’ve personally seen RPBG miswired outlets in at least a few dozen old campgrounds, boat docks, churches and sound stages. In fact, anytime I see a brand-new 3-prong grounded outlet in an old building, I’m doubly careful to test it for RPBG miswiring since electricians still take this inexpensive shortcut, even though it’s a big code violation.

A Non-Contact Voltage Tester can find an RPGB

The only simple way to detect an RPBG condition is by using a Non-Contact Voltage Tester (NCVT), which is a procedure I developed and pioneered for the RV industry. As you can see above, a NCVT will easily find an outlet that’s been miswired with a RPBG condition.

I’ve discussed this RPBG condition with every EMS/Surge-Protector manufacturer in the market and currently none of their products can detect or disconnect your RV from one. However, I’ve been working on a possible solution that would allow an EMS/surge-protector to alert you of this hot-chassis condition, no matter what the cause.

Watch this video on using an NCVT to find a hot-skin…

In the meantime, be sure to use your Non-Contact Voltage Tester every time you hook up to shore power to make sure the campground pedestal or garage outlet and your RV are safe from any hot-skin voltages. For those of you who don’t know what a Non-Contact Voltage Tester (NCVT) is or how to use one, watch my video below.

More on this later, but the important takeaway is to never ignore a shock when touching your RV. If you do feel a shock, unplug from shore power immediately until you can find the cause and repair it.

Let’s play safe out there… Mike

16 thoughts on “What is a Reverse Polarity Bootleg Ground?”

    1. It can easily occur on a 30-amp outlet, but pretty difficult to happen on a 50-amp outlet. However, a 20-amp to 50-amp dogbone adapter plugged into a RPBG home outlet would create a full-current 120-volt hot-skin voltage on a 50-amp RV.

  1. Hi Mike, As an alternative to running new cable with ground wire in existing installations, code allows the use of a Class A GFCI. If the 1st receptacle in the circuit is replaced with a GFCI and the rest of the circuit is connected to the load side of the GFCI the circuit is protected. This may not be viable with a 30 amp or 50 amp receptacle due to the cost of the GFCI . This is permitted by Canadian Electrical Code C22.1-18 Rule 26-702(2). I’m guessing that the NEC would have a similar provision?

    1. That is true and there is an exception in NEC allowing the use of a Class-A GFCI instead of an EGC ground on a 20-amp branch circuit. But a Class-A GFCI trips at 5mA, and that will often cause nuisance tripping on any feeder circuit powering an RV shore connection.

  2. My Progressive EMS surge protector has given me an “E-1” before (rev. polarity) and it won’t pass power to the rv in that condition. I don’t know if the missing ground error will make it do the same thing but as you stated there’s no error code for a bootlegged ground.

    1. A EMS Surge Protector can’t recognize a bootleg ground. There must be a reversed hot and neutral in the pedestal outlet.

    1. Yes, it requires a screwdriver stuck in the dirt to establish earth potential, but is a pretty simple test procedure. I’ve seen this happen at a few old campgrounds that had pre-1970 cabins. They originally ran 2-wire power (hot and neutral) but later changed out to grounded outlets in the cabins. This would have worked and not been a code violation with GFCI receptacles, but their maintenance guy just did a bootleg ground so his 3-light test told him everything was okay when it wasn’t.

  3. My house was built in 1956 and had all 2-prong outlets. Fortunately the entire house was wired in armored cable (BX) with the metallic sheath bonded to the main entrance, so I was able to upgrade the outlets to 3-prong with a jumper from the ground lug to the box.

    1. Note that some state and county inspectors will not allow armored (BX) cable to act as the EGC ground conductor, but many do allow it.
      I’ve also set up large sound systems in Texas, and they use metallic conduit for the ground conductor. But I’ve never seen this sort of grounding in Maryland.
      I’ve also designed large Audio/Video systems for houses of worship in California, and the earthquake codes for the electrical and alarm systems in commercial buildings drove me nuts.
      Code was super crazy complicated in downtown Washington DC when I did political gigs such as presidential inaugurations, but in fairgrounds right outside of the beltway they appeared to have zero inspection. Ugh!
      So my point is, always check with your local AHJ (Authority Having Jurisdiction) inspector to confirm local code compliance.

  4. Mike,
    Am I overthinking this? But using a VOM with a RPBG, if I check for voltage from the hot side to ground, I would not see voltage when I should. And conversely, if I checked for voltage from the neutral to ground, I should not see voltage, but with RPBG, I would see voltage. Have I got ‘my’ wiring crossed ? At least this should trigger my noodle, that something is not correct. JAM!

    1. I think clarifying the differences between Earth-Ground, Outlet-Ground and Chassis-Ground will help.
      Earth-Ground is the dirt beneath your feet.
      Outlet-Ground is the ground contact in a receptacle that should be connected to the shore power EGC. (Equipment Grounding Conductor)
      Chassis-Ground is all the metal parts of your RV bonded to the EGC including the chassis, skin, hitch, bumpers, etc…
      With an RPBG condition if you measure between the hot leg to Earth-Ground you’ll see close to zero volts. And an RPBG outlet condition between the Neutral and Outlet-Ground to Earth-Ground will measure around 120 volts.
      But most testing procedures use the Chassis-Ground or Outlet-Ground as the reference, which is why 3-light outlet testers, advanced outlet analyzers, and metering between H-N-G with a voltmeter will not be able to discover an RPBG. But measuring 120 volts between Earth-Ground and the Neutral/Outlet-Ground is a good indicator of an RPBG.